The problem as it presented itself
The brief was a specification, not a failure: the customer needed an illuminance figure guaranteed at the task plane, and the existing installation delivered a compliant average with unusable uniformity. The average number had been measured from a single point at the centre of the room, which is the first thing to check in any lighting complaint.
The diagnosis came from a measurement grid rather than a specification sheet. Taking readings on a grid across the working area showed the problem was geometric, not photometric: the fixture spacing was too wide for the mounting height, so the centre of the room was over-lit while the areas where work actually happened fell below target.
- Measure on a grid, not at a point. A single centre reading hides exactly the problem that matters.
- Check spacing-to-mounting-height before changing fixtures. Most uniformity complaints are layout problems.
- Separate the average from the task plane. Illuminance at floor level says little about illuminance at the work surface.
The fix was a layout change rather than a product change: closer spacing and a different mounting height brought the whole working plane into range. No luminaire was replaced. This is why the geometric check comes before the product check.
A school district needed to renovate lighting in 200 classrooms. Existing fluorescent fixtures caused eye strain, flicker headaches, and poor color rendering. New fixtures needed to meet GB 50034 standard (300+ lux, UGR<19, Ra80+).
Queendom Solution
Queendom installed EDU-36W-Ra90 panel lights with 300-500 lux, UGR<19, Ra90, and flicker-free drivers. The system achieved 60% energy savings and improved student concentration per teacher feedback surveys.
Key Advantages:
- 300-500 lux: Exceeds GB 50034 standard
- UGR<19: Glug-free for reduced eye strain
- Ra90 CRI: Accurate color for learning materials
- Flicker-free: <1% flicker index (no headaches)
- 60% energy savings vs fluorescent

Product Specifications
| Parameter | Specification |
|---|---|
| Fixture | EDU-36W-Ra90 LED panel light |
| Power | 36W (replaces 72W fluorescent) |
| Illuminance | 300-500 lux at desk level |
| UGR | <19 (glare-free) |
| CRI | Ra90 |
| Flicker Index | <1% |
| CCT | 5,000K (daylight white) |
| Lifespan | 50,000+ hours |
| Certifications | CE / RoHS / CCC / GB 50034 |
Application Scenarios
Standard Classroom
8 panels, 300 lux, UGR<19, 200 sqm
Art Room
Ra95 option, 500 lux, 5,000K for color accuracy
Library
Warm 4,000K, anti-glare louvers, reading comfort
Case Direction
School renovation: 200 classrooms, 36W LED panels, 300 lux UGR<19 Ra90, 60% energy savings, improved student comfort.