The problem as it presented itself

The brief was a specification, not a failure: the customer needed an illuminance figure guaranteed at the task plane, and the existing installation delivered a compliant average with unusable uniformity. The average number had been measured from a single point at the centre of the room, which is the first thing to check in any lighting complaint.

The diagnosis came from a measurement grid rather than a specification sheet. Taking readings on a grid across the working area showed the problem was geometric, not photometric: the fixture spacing was too wide for the mounting height, so the centre of the room was over-lit while the areas where work actually happened fell below target.

  • Measure on a grid, not at a point. A single centre reading hides exactly the problem that matters.
  • Check spacing-to-mounting-height before changing fixtures. Most uniformity complaints are layout problems.
  • Separate the average from the task plane. Illuminance at floor level says little about illuminance at the work surface.

The fix was a layout change rather than a product change: closer spacing and a different mounting height brought the whole working plane into range. No luminaire was replaced. This is why the geometric check comes before the product check.

A school district needed to renovate lighting in 200 classrooms. Existing fluorescent fixtures caused eye strain, flicker headaches, and poor color rendering. New fixtures needed to meet GB 50034 standard (300+ lux, UGR<19, Ra80+).

Queendom Solution

Queendom installed EDU-36W-Ra90 panel lights with 300-500 lux, UGR<19, Ra90, and flicker-free drivers. The system achieved 60% energy savings and improved student concentration per teacher feedback surveys.

Key Advantages:

  • 300-500 lux: Exceeds GB 50034 standard
  • UGR<19: Glug-free for reduced eye strain
  • Ra90 CRI: Accurate color for learning materials
  • Flicker-free: <1% flicker index (no headaches)
  • 60% energy savings vs fluorescent
classroom-lighting-renovation

Product Specifications

ParameterSpecification
FixtureEDU-36W-Ra90 LED panel light
Power36W (replaces 72W fluorescent)
Illuminance300-500 lux at desk level
UGR<19 (glare-free)
CRIRa90
Flicker Index<1%
CCT5,000K (daylight white)
Lifespan50,000+ hours
CertificationsCE / RoHS / CCC / GB 50034

Application Scenarios

Standard Classroom

8 panels, 300 lux, UGR<19, 200 sqm

Art Room

Ra95 option, 500 lux, 5,000K for color accuracy

Library

Warm 4,000K, anti-glare louvers, reading comfort

Case Direction

School renovation: 200 classrooms, 36W LED panels, 300 lux UGR<19 Ra90, 60% energy savings, improved student comfort.